변전소 조상 설비간의 협조 제어를 위한 EMTP 과도해석모형 개발
정기석(Ki-Seok Jeong),백영식(Young-Sik Baek),박지호(Ji-Ho Park),장병훈(Byung-Hoon Chang),이현철(Hyun-Chul Lee),이근준(Geun-Joon Lee) 대한전기학회 2009 대한전기학회 학술대회 논문집 Vol.2009 No.7
This paper proposes coordinative control method between STATCOM installed within substation and other reactive power resources including Shunt Reactors and Shunt Capacitors and OLTC. Voltage/Reactive power control has various difficult aspects to control because of analysis and system dynamics error. This coordinative control method suggests practical algorithm regarding system voltage and reactive power status which is easy to implement in substation basis. In normal status, STATCOM-Shunts-OLTC are in operation. The proposed algorithm is tested and verified in EMTP/RV. And this is expected to be applied to control multiple reactive power devices combined with SCADA/EMS system.
피뢰기를 고려한 자가용 전기설비 인입선로의 직류누설전류시험에 관한 연구
정기석(Ki-Seok Jeong),길형준(Hyoung-Jun Gil) 대한전기학회 2018 전기학회논문지 Vol.67 No.1
Private electrical facilities are judged whether it is suitable for the insulation aging condition of their incoming underground cables using DC leakage current test method. In the case where the service point of utility is the secondary side of cut out switch installed in the electric pole, there is a problem that it is difficult to separate the lightning arresters(LA) because of their high position of the pole. Therefore, the field test voltage is applied at value lower than DC 30 kV, which are stated in the inspection guideline. However, this test could reduced the insulation performance of the LA by accelerating the electrical stress of the metal oxide varistor element in the pre-breakdown region. In this study, we analyzed the relationship between the DC test voltage and the leakage current using the non-destructive DC high voltage equipment with leakage current measurement function. The results show that the leakage current increases sharply above the specified test voltage. As a consequence, it could be contributed to improve insulation aging inspection method by selecting the possible test area on the VI characteristic curve of the pre-breakdown area of the LA.
변전소 전압안정화를 위한 STATCOM과 기존 조상 설비간의 지역 무효전력 협조제어에 관한 연구
정기석(Ki-Seok Jeong),장병훈(Byun-Hoon Chang),이현철(Hyun-Chul Lee),이근준(Geun-Joon Lee),백영식(Young-Sik Baek) 대한전기학회 2010 전기학회논문지 Vol.59 No.3
Installation of FACTS(Flexible AC Transmission System) device can maximize utilization of existing power facilities and reliability of power system. STATCOM has excellent characteristics in operating cost, maintaining facilities, loss and so on. However, STATCOM has a disadvantage of facility cost over capacity. So it is effective to coordinate STATCOM and existing external bank(capacitor and reactor) and OLTC(On Load Tap Changer). This paper mainly proposes coordinative control method between STATCOM installed within substation and other reactive power resources including Shunt Reactors and Shunt Capacitors and OLTC for voltage stability improvement. The proposed coordinative control method is developed for the STATCOM of Mi-gum substation and the simulation results of EMTP/RV model show the effectiveness of the proposed method.