3상 자속결합형 초전도 한류기의 1선지락 사고시 전압증가 및 재폐로 동작에 따른 특성 분석
하경훈(Kyoung-Hun Ha),최효상(Hyo-Sang Choi),박형민(Hyoung-Min Park),조용선(Yong-Sun Cho),정병익(Byoung-Ik Jung),최수근(Soo-Geun Choi),오금곤(Geum-Gun Oh),김덕구(Duk-Gu Kim),고성필(Sung-pil Ko) 한국조명·전기설비학회 2010 한국조명·전기설비학회 학술대회논문집 Vol.2010 No.9월
The electric pewer demand has increased. As a result, we need to change a circuit breaker for bigger capacity one but it has sorre problems. In order to solve the difficulties according to change a circuit breaker, some alternative plans are suggested. One of them is to apply a SFCL in the electric pewer system The SFCL has the ability to reduce a fault current with an existing circuit breaker and it can protect an electric pewer system. In this paper, we composed a three phase flux-coupling type SFCL and analyzed a recovery characteristic according to reclosing operation with an increase in voltage. If the recovery time is delayed than we are expected, it could be a loss in the normal state. So we have to improve a recovery characteristic for application of SFCL to electric pewer svstem.
자속결합형 초전도 한류기의 불평형 사고시 과도특성 해석
정병익(Byung-Ik Jung),최효상(Hyo-Sang Choi),조용선(Yong-Sun Cho),하경훈(Kyoung-Hun Ha),최수근(Soo-Gun Choi),고성필(Sung-Pil Ko) 한국조명.전기설비학회 2011 한국조명·전기설비학회 학술대회논문집 Vol.2011 No.11
현대의 생활환경 변화와 산업의 발달로 인해 전력사용량이 해가 갈수록 증가하고 있다. 이러한 전력수요 증가에 맞춰 전기설비의 증설이 필요하지만 설비 증설로 인해 사고시 사고전류의 크기가 증가하고 있다. 이러한 사고전류의 크기는 계통의 주차단기 차단내력을 넘어서게 되고 결국 대용량 차단기로의 교체가 필요하게 되었다. 이러한 상황에서 사고전류의 크기를 제한하여 기존 차단기의 차단내력을 초과하지 않게 해주기 위한 초전도 한류기가 고안되었다. 본 논문에서는 자속결합형 초전도 한류기의 계통 적용시 과도 상태를 분석함으로써 한류기의 적용이 계통 전체에 미치는 영향을 분석하였다. 본 연구에서는 계통 사고의 대부분을 차지하는 1선 지락 사고시(불평형사고)의 사고전류를 분석하였고, 불평형 사고 해석을 위해 대칭좌표법을 이용하였다. 본 초전도 한류기의 구조는 변압기와 초전도 한류소자를 이용한 구조로써 변압기 1차측 코일의 권수를 증가시킴에 따라서 각 대칭분 전류(영상, 정상, 역상 전류)의 크기가 감소하는 것을 확인할 수 있었다.