      제조 사업장의 환풍기 화재위험성 조사

      한글로보기

      https://www.riss.kr/link?id=A99793396

      • 0

        상세조회
      • 0

        다운로드
      서지정보 열기
      • 내보내기
      • 내책장담기
      • 공유하기
      • 오류접수

      부가정보

      다국어 초록 (Multilingual Abstract)

      he short circuit and overload is presented by main cause of electrical fire. However, 85% of the fan directly connected the outlet box without switch in total 110 fans as a research in manufacturing industries. In installation direction of vertical ty...

      he short circuit and overload is presented by main cause of electrical fire. However, 85% of the fan directly connected the outlet box without switch in total 110 fans as a research in manufacturing industries. In installation direction of vertical type fans which was placed on the horizontal surface, only 39 vertical type fans were placed on vertical surface and 71 fans were placed on the horizontal type. The installation direction of the fans warns of the risk of the fire hazard due to the motor stall to the user manual of the maker. However, it is the representative nonconformity example of construction which the people or builder disregards. In addition, the condition of ground connection with the earth leakage prevention was investigated in grounding of 5 fans, non-grounding of 105 fans. The double insulation structure is generally used for small fan and it can’t connect ground wire as electric plug of non-grounding type. However, industrial iron fan needs ground wire for electric leakage and to protect against electric shock.

      더보기

      목차 (Table of Contents)

      • Abstract
      • 1. 서론
      • 2. 본론
      • 3. 결론
      • References
      • Abstract
      • 1. 서론
      • 2. 본론
      • 3. 결론
      • References
      더보기

      참고문헌 (Reference)

      1 이춘하, "전동기 소손에 대한 화재 원인 분석에 관한 연구" 한국화재소방학회 21 (21): 59-64, 2007

      2 최선호, "공동주택 주방 배기 시스템 구성 요소별 정압손실 특성에 따른 주방환기 성능에 관한 실험적 연구" 대한건축학회 28 (28): 269-276, 2012

      3 "http://www.nema.go.kr/nema_cms_iba/show_nema/board/board1s/view.jsp?cNo=421070&c_relation=18&check_the_code=2&check_the_num=116&check_up_num=113&pageNo=1"

      4 "http://www.nema.go.kr/nema_cms_iba/show_nema/board/board1s/view.jsp?cNo=420933&c_relation=18&check_the_code=2&check_the_num=116&check_up_num=113&pageNo=1"

      5 "http://www.nema.go.kr/nema_cms_iba/show_nema/board/board1s/view.jsp?cNo=337241&c_relation=18&check_the_code=2&check_the_num=116&check_up_num=113&pageNo=1"

      6 "http://www.nema.go.kr/nema_cms_iba/show_nema/board/board1/view.jsp?cNo=393720&c_relation=25&check_the_code=1&check_the_num=135&check_up_num=110&pageNo=1"

      7 Jin-Man Choi, "The Fire Investigation Introduction" Sungandang 228-235, 2010

      8 Hyeog-Soo Kim, "The Analysis of the Fire Hazard According to Layer Short-Circuit of Motor Winding for the Fan" 135-139, 2000

      9 H. S. Joe, "Study on the Mechanism, Properties & State of the Ignitible, and Fire Investigation Technique to Electric & Ventilating Fans" 109-125, 2008

      10 Jun-Won Song, "Study on Selection of Optimal Bathroom Ventilating fans Based on Measurements of Performance Appraisal and Flow Resistance in Exhaust Duct" 672-680, 2002

      1 이춘하, "전동기 소손에 대한 화재 원인 분석에 관한 연구" 한국화재소방학회 21 (21): 59-64, 2007

      2 최선호, "공동주택 주방 배기 시스템 구성 요소별 정압손실 특성에 따른 주방환기 성능에 관한 실험적 연구" 대한건축학회 28 (28): 269-276, 2012

      3 "http://www.nema.go.kr/nema_cms_iba/show_nema/board/board1s/view.jsp?cNo=421070&c_relation=18&check_the_code=2&check_the_num=116&check_up_num=113&pageNo=1"

      4 "http://www.nema.go.kr/nema_cms_iba/show_nema/board/board1s/view.jsp?cNo=420933&c_relation=18&check_the_code=2&check_the_num=116&check_up_num=113&pageNo=1"

      5 "http://www.nema.go.kr/nema_cms_iba/show_nema/board/board1s/view.jsp?cNo=337241&c_relation=18&check_the_code=2&check_the_num=116&check_up_num=113&pageNo=1"

      6 "http://www.nema.go.kr/nema_cms_iba/show_nema/board/board1/view.jsp?cNo=393720&c_relation=25&check_the_code=1&check_the_num=135&check_up_num=110&pageNo=1"

      7 Jin-Man Choi, "The Fire Investigation Introduction" Sungandang 228-235, 2010

      8 Hyeog-Soo Kim, "The Analysis of the Fire Hazard According to Layer Short-Circuit of Motor Winding for the Fan" 135-139, 2000

      9 H. S. Joe, "Study on the Mechanism, Properties & State of the Ignitible, and Fire Investigation Technique to Electric & Ventilating Fans" 109-125, 2008

      10 Jun-Won Song, "Study on Selection of Optimal Bathroom Ventilating fans Based on Measurements of Performance Appraisal and Flow Resistance in Exhaust Duct" 672-680, 2002

      11 John D. DeHaan, "Kirk’s Fire Investigation" Dooyangsa 556-560, 2011

      12 "KS C 9304, Ventilating Fans"

      13 Hyun-Rok Cha, "Inverter Motor Drive System Development for High Static Pressure Ventilation Fan" 1193-1194, 2008

      14 Seung-Bok Choi, "Identifying a ventilation fan with flesh eyes" 4 (4): 70-74, 2004

      15 B. J. Rho, "Fundamental Design and Test of Seam Blade in Ventilation Fan" 1-5, 2006

      16 Jung-Il Lee, "Fire investigation business’" Junghunsa 520-523, 2009

      17 Sung-sam Kim, "Fire Cause Analysis of Ventilation Fan through the Fire Events" 186-187, 2013

      18 Chung-Seog Choi, "Electrical Fire Engineering" DongHwa Publishing 165-166, 2000

      19 Robert A. Yereance, "Electrical Fire Analysis" 191-193, 2010

      20 Durham, Marcus O, "Electrical Failure Analysis" Dream point Publishers 47-48, 2011

      21 J. Park, "Design of multipurpose ventilator for a vehicle using air-multiplier" 1131-1132, 2010

      22 Seung-Bin Lim, "Design of High efficiency 2phase Brushless DC Motor for Ventilation Fan" 17-19, 2009

      23 S. T. Kwon, "Core Professional Engineer Fire Protection" Yeamoonsa 67-75, 2007

      24 Pil-Dong Song, "A Study on the Ventilation Performance Estimation of Marketing Ventilation Fan Used in the Apartment House Kitchen" 315-320, 2002

      25 Jeong-Tae Jang, "A Study on the Countermeasure and Analysis Cause of Electrical Fire" 7 (7): 157-168, 2011

      26 Sung-Ho Hong, "A Experimental Study on the Electrical Fire Hazards Analysis of Electric Fan" 344-349, 2007

      더보기

      동일학술지(권/호) 다른 논문

      동일학술지 더보기

      더보기

      분석정보

      View

      상세정보조회

      0

      Usage

      원문다운로드

      0

      대출신청

      0

      복사신청

      0

      EDDS신청

      0

      동일 주제 내 활용도 TOP

      더보기

      주제

      연도별 연구동향

      연도별 활용동향

      연관논문

      연구자 네트워크맵

      공동연구자 (7)

      유사연구자 (20) 활용도상위20명

      인용정보 인용지수 설명보기

      학술지 이력

      학술지 이력
      연월일 이력구분 이력상세 등재구분
      2027 평가예정 재인증평가 신청대상 (재인증)
      2021-01-01 평가 등재학술지 유지 (재인증) KCI등재
      2018-01-01 평가 등재학술지 유지 (등재유지) KCI등재
      2015-01-01 평가 등재학술지 유지 (등재유지) KCI등재
      2014-01-08 학술지명변경 외국어명 : 미등록 -> Journal of the Korean Institute of Illuminating and Electrical Installation Engineers KCI등재
      2011-01-01 평가 등재학술지 유지 (등재유지) KCI등재
      2009-01-01 평가 등재학술지 유지 (등재유지) KCI등재
      2007-01-01 평가 등재학술지 유지 (등재유지) KCI등재
      2004-01-01 평가 등재학술지 선정 (등재후보2차) KCI등재
      2003-01-01 평가 등재후보 1차 PASS (등재후보1차) KCI등재후보
      2001-07-01 평가 등재후보학술지 선정 (신규평가) KCI등재후보
      더보기

      학술지 인용정보

      학술지 인용정보
      기준연도 WOS-KCI 통합IF(2년) KCIF(2년) KCIF(3년)
      2016 0.17 0.17 0.19
      KCIF(4년) KCIF(5년) 중심성지수(3년) 즉시성지수
      0.18 0.17 0.342 0.05
      더보기

      이 자료와 함께 이용한 RISS 자료

      나만을 위한 추천자료

      해외이동버튼