This paper proposes a control algorithm for 3-phase 4-wire series active power filter. This control algorithm compensates harmonics and neutral line currents which are generated by balanced or unbalanced nonlinear loads. The advantage of this control ...
This paper proposes a control algorithm for 3-phase 4-wire series active power filter. This control algorithm compensates harmonics and neutral line currents which are generated by balanced or unbalanced nonlinear loads. The advantage of this control algorithm is direct extraction of compensation voltage references. Therefore, calculation time is shorten and the performance of series active power filter is improved. Compensation principle of the proposed control algorithm is presented in detail. Experimental results are shown to verify the effectiveness of the proposed control algorithm.