The purpose of this study was to investigated the ELF-MF emission level of various environments such as 258 facilities near located to high voltage transmission lines and 120 high voltage transmission lines, 17 underground cable lines. In addition, EL...
The purpose of this study was to investigated the ELF-MF emission level of various environments such as 258 facilities near located to high voltage transmission lines and 120 high voltage transmission lines, 17 underground cable lines. In addition, ELF-MF reduction rate according to separation distance was calculated by using simulations.An appropriate separation distance showing below 4mG was at least 70m. In the case of the appropriate separation distance for 120 high voltage transmission lines, 154kV required 20m of separation distance and 345kV required 60m of separation distance. The simulation results showed that the appropriate separation distance showing below 4mG was 40m and 60m for overhead 154kV and 345kV respectively. To adjust the worst conditions considering the aspects of environmental impact assessment study and the electric power currents that will increase in the future, the appropriate minimum separation distance for HVTL is judged to be above 70m in this study. Thus, there is a need to establish the greenbelt or buffer zone within 70m so as to create an environment in which the receptors are not exposed and thereby eliminate the risk factors of ELF-MF against humans.