A bench type ammonia-water absorber heat exchange cycle was tested by varying the system charging concentration, refrigerating valve opening and weak solution flow rate. It was observed that the cooling capacity was increased as the system charging co...
A bench type ammonia-water absorber heat exchange cycle was tested by varying the system charging concentration, refrigerating valve opening and weak solution flow rate. It was observed that the cooling capacity was increased as the system charging concentration was increased. Optimum system charging concentration was found for the coolong capacity of the system. The opening rate of refrigerant expansion valve had a direct influence on the refrigerant sub-cooling at the condenser outlet. Optimum sub-cooling was found to be 0~4$^{\circ}C$. As the weak solution flow rate increased the concentration of strong solution and the evaporating pressure decreased. There existed a optimum weak solution flow rate which maximized the cooling capacity and COP.