The purpose of this paper is to review the understanding of pollution causes in the excitation system and how to solve the problem. The cause of the problem was in-leakage of bearing lubricant oil through the gap between rotor and outer in the air def...
The purpose of this paper is to review the understanding of pollution causes in the excitation system and how to solve the problem. The cause of the problem was in-leakage of bearing lubricant oil through the gap between rotor and outer in the air deflector, which was triggered by a negative pressure with respect to the operation of a collector ring fan in the collector house. In order to prevent exciting current transmission equipment pollutant, the reduction of the negative gage pressure of the inside of collector house is required. The protection in-leakage of bearing lubricant oil through the gap between rotor and outer of the air deflector are necessary. The reduction of the inside diameter of air deflector and the expansion of inlet filter of collector house are inevitable.