The purpose of this paper is to determine the cut off flowrate regions of the overflow valve in using L.P gas vassels. The experimental methods were employed to measure the cut off flowrate in the state of constant pressure by using the $N_2$ gas. 1) ...
The purpose of this paper is to determine the cut off flowrate regions of the overflow valve in using L.P gas vassels. The experimental methods were employed to measure the cut off flowrate in the state of constant pressure by using the $N_2$ gas. 1) To determine the optimum cut off flowrate regions, Hose length are required 0.5 meters. 2) Cut off fowrate regions about the each pressure can be suggested as follows. A) Cut off flowrate rigions are $2.0-4.0m^3/hr$ at the pressure of the $1Kg_f/cm^2$. B) Cut off flowrate rigions are$7.0-10.0m^3/hr$ at the pressure of the $10Kg_f/cm^2$.