The pilot test of a new alternative for small wastewater treatment system has been conducted for two years. It consists of a hybrid bioreactor and the expert system including the process control logic, PLC system, and HMI for the process automation. I...
The pilot test of a new alternative for small wastewater treatment system has been conducted for two years. It consists of a hybrid bioreactor and the expert system including the process control logic, PLC system, and HMI for the process automation. In order to monitor and remote control its status, the real-time data was transferred from the on-site control center to the central station via a wireless local area network. More efficient and stable performances were observed at automatic operating mode compared with the manual. On an average, COD, SS, T-N and T-P concentrations in the effluent from the hybrid bioreactor were less than 14, 7, 12 and 0.9 ㎎/L, respectively. According to the result from pilot tests, the quality of treated wastewater with sand filtration was enough to be utilized again.