Fluid flow and structural analyses of an electronic expansion valve (EEV) using CO2 as a working refrigerant are carried out to estimate the mass flow rate and maximum stress. An engineering sample EEV that the orifice diameter is 1.8 mm was fabricate...
Fluid flow and structural analyses of an electronic expansion valve (EEV) using CO2 as a working refrigerant are carried out to estimate the mass flow rate and maximum stress. An engineering sample EEV that the orifice diameter is 1.8 mm was fabricated. The mass flow rates were measured at various EEV inlet temperatures and pressures for several EEV openings using experimental heat pump system. The sample EEV has over 35 ㎫ burst pressure and the maximum mass flow rate of CO2 through the EEV increased to 100 g/s at full opening condition.