http://chineseinput.net/에서 pinyin(병음)방식으로 중국어를 변환할 수 있습니다.
변환된 중국어를 복사하여 사용하시면 됩니다.
Study of PD Location in Generators by PD Pulses Propagation
YangChun Cheng,ChengRong Li,Wei Wang 한국전기전자재료학회 2006 Transactions on Electrical and Electronic Material Vol.7 No.5
When a partial discharge takes place at the stator of a generator, the electrical pulse will propagate along the stator bars and the capacitor chains formed by the end part of the stator winds. On the first path, the pulse propagates as a travel wave at slow speed. On the second path, the pulse propagates at quick speed. Based on the data of the experiments on a real 50 MW steam generator, the author has found the pulses can propagate by magnetic field of the stator winding. It was studied that how to locating the partial discharge by signals coming from the different paths, including the features of signals on the two paths at time domain and frequency domain, the measurement frequency rang of the signals, the blind area, the advantage and disadvantage of this method.