최효상(Hyo-Sang Choi),최창주(Chang-Joo Choi),이상일(Sang-Il Lee),정수복(Soo-Bok Chung),오금곤(Geum-Kon Oh),정헌상(Hun-Sang Chung) 한국조명·전기설비학회 2003 한국조명·전기설비학회 학술대회논문집 Vol.2003 No.-
We analysed the operating properties of resistive type superconducting fault current limiters (SFCLs) based on YBCO thin films with a single line-to-ground fault. When a single line-to-ground fault occurred the short circuit current of a fault phase increased up to about 6 times of transport currents immediately after the fault instant and was effectively limited to the designed current level within 2 ms by the resistance development of the SFCL. The fault currents of the sound phases almost did not change because of their direct grounding system. The unsymmetrical rates of a fault phase were distributed from 6.4 to 1.4. It was found that the unsymmetrical rates of currents were noticeably improved within one cycle after the fault instant. We calculated the zero phase currents for a single line-to-ground fault using the symmetrical component analysis. The positive sequence resistance was reduced remarkably right after the fault but eventually approached the balanced positive resistance component prior to the system fault. This means that the system reaches almost the three-phase symmetrical state in about 60 ms after the fault. The ground currents were almost 3 times of the zero phase currents since most of the fault currents flowed through the grounding line.