The auricular cartilage grafts have been widely used in replacement of the temporomandibular joint disk. Cartilage grafts itself have a low metabolism and high survival rate after grafting. In processing the grafting materials, it was important to preserve the properties of chondrocyte proper. We used 15% glycerol and 10% DMSO (Dimethyl Sulfoxide) solutions for cartilage fixation before deep freezing. We have performed the allogenic auricular cartilage graft in the temporomandibular joint of 20 rabbits which 10 specimen was treated with 15% glycerol and the other 10 specimen was treated with 10% DMSO respectively and examined in 1, 2, 4, 6 and 8 weeks after operation histopathologically. The result were : 1. Inflammatory cell infiltration around the grafted material appeared more glycerol groups than DMSO groups at 1 week, but each group has no differences after 2 weeks. 2. Degenerative changes of grafted auricular chondrocytes were more deveolped in glycerol group than DMSO groups till 4 weeks, but there were no differences between two groups after 6 weeks. 3. Fibrous union between grafted fragment and mandibular condyle was prominent in DMSO group. 4. Vascular proliferation of the grafted auricualr cartilage was more developed in DMSO groups than glycerol group in early stage. 5. Amount of the additional growth of grafted auricular cartilage was more existed in DMSO groups than glycerol group. 6. General survival rate after grafting was more prominent in DMSO group. In summary, allogenic auricular cartilage grafts treated with 15% glycerol and 10% DMSO solution have supported to survivalbility as a cryopreservative agents, especially DMSO groups have little inflammatory cell infiltration in early stages and degenerative changes and additional growth are more prominent than glycerol groups.
GIS 예방진단시스템 주파수 분석장치 성능개선 및 검증
김원규(Won-Gyu Kim),김민수(Min-Soo Kim),백영식(Young-Sik Baek) 대한전기학회 2015 전기학회논문지 Vol.64 No.3
This paper shows the design improvement and test model of FAU (Frequency Analysis Unit) in PDD (Partial Discharge Diagnosis system) for 800kV GIS (Gas Insulated Switchgear). We found some problems during operation of previous FAU, such as the aging of fiber-optic converter that can cause communication error, the malfunction of signal analysis circuit etc. And then we solved those problems by design improvement and verified the performance through type test. To monitor partial discharge, the performance of UHF sensor is important but the performance of frequency analysis unit is also very important. So we solved communication error, the malfunction of signal analysis circuit and then increased the operation reliability of FAU by improving fiber-optic converter and signal analysis circuit. Accredited testing laboratory carried out the performance verification test according to performance test criteria and procedure of reliability test standards, IEC-60225, 61000 and 60068 etc. We confirmed the test results which correspond with the performance test criteria.
김원규(Won-Gyu Kim),김민수(Min-Soo Kim),백영식(Young-Sik Baek) 대한전기학회 2014 전기학회논문지 Vol.63 No.12
This paper shows the developed new lightning arrester LCM (Leakage Current Measuring device) which is important element of GIS (Gas Insulated Switchgear) Preventive & Diagnostic system and verify its performance though strengthened test standards. The existing lightning arrester LCM was modified to solve measuring errors which happened frequently. At first, we explained the principle of measuring leakage current. Through analyzing some problems which the existing LCM have. we got some improvable items. For the performance verification of the improved LCM, we manufactured prototype LCM which is applied some improvable items such as improving LCM circuit, adding protection circuit, optimizing inner structure of LCM and changing ground design. After then we carried out the performance test. Accredited testing laboratory carried out the performance verification test according to performance test criteria and procedure of reliability test standards, IEC-60225, 61000 and 60068 etc. We confirmed the test results which correspond with the performance test criteria. Also, we confirmed the performance of the improved LCM installed & being operated at G Substation through the immunity test against the normal noise and open/close surge etc.
부분방전검출 신뢰도 향상을 위한 UHF 센서개선 및 성능검증
김원규(Won-Gyu Kim),김민수(Min-Soo Kim),백영식(Young-Sik Baek) 대한전기학회 2014 전기학회논문지 Vol.63 No.10
GIS(Gas Insulated Switchgear) is important power apparatus which have strong dielectric strength, supply electric power and is a part of the power system. Most substation type is configured as GIS. Recently, because of continuous increasement of GIS demand resulted from high quality & big capacity of electric power, the necessity of the preventive & diagnosis system is being expanded gradually. GIS partial discharge occurred on the UHF band is detected effectively by the method to IEC 60270 that recommend to be able to detect the apparent minimum discharge, 5 pC. Additionally, the UHF sensor should be installed to detect PD signal if Partial discharge signal, 5 pC occur in every part of GIS. Currently PD diagnosis system applying UHF sensor for GIS with various voltage level like 154 kV, 345 kV, 765 kV have been operated. And it is necessary to measure and analyze insulation breakdown phenomenon of inside GIS exactly. In this paper, we proposed Fat-dipole patch UHF sensor that is developed and more sensitive, excellent wide-range characteristic than the exising UHF sensor. And we performed KERI (Korea Electrotechnology Research Institute) reference test, which showed the excellent result for the all tests.