김선창(Seon-Chang Kim),김영률(Young-Lyoul Kim),이상재(Sang-Jae Lee),전동순(Dong-Soon Jeon),최장현(Jaug-Hyeon Choi),권혁민(Hyeok-Min Kwon),이창준(Chang-Jun Lee) 대한설비공학회 2009 대한설비공학회 학술발표대회논문집 Vol.2009 No.-
This paper presents the optimization process of liquid desiccant cooling cycle using LiCl aqueous solution as a working fluid. Operating conditions and design factors for heat exchangers were optimized by response surface method. As a result, we obtained the 7.297 ㎾ of cooling capacity and 0.788 of COP at optimized condition. Effect of dT<SUB>hw</SUB> on system performances was also examined. As dT<SUB>hw</SUB> increases, the cooling capacity increases and COP decreases.